Christie-digital-systems XENON CONSOLE Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 63
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
SLC Series Xenon Console
4-6 CHRISTIE DIGITAL SYSTEMS
August 7, 2003
AC Wiring Hook-Ups
AC AMPERES WIRE DIAMETER (AWG) PER CABLE LENGTH
PER PHASE 50 FT 100 FT 150 FT 200 FT 250 FT
0 - 10 14 14 12 10 10
11 - 15 14 12 10 8 6
16 - 20 12 10 8 8 6
21 - 25 10 10 8 6 4
26 - 35 8 8 6 4 4
36 - 45 6 6 4 4 3
46 - 60 4 4 4 3 1
61 - 70 3 3 3 2 1
71 - 80 2 2 2 1 1/0
Figure 4-4: Minimum Wire Sizes for AC Connections
DC Wiring Hook-Ups
DC AMPERES WIRE DIAMETER (AWG) PER CABLE LENGTH
PER PHASE 25 FT 50 FT 75 FT 100 FT
20 10 10 8 6
40 10 8 6 4
60 8 6 4 2
80 4 4 2 1
100 4 3 1 1/0
125 3 1 1/0 2/0
150 3 1 2/0 3/0
200 2 1/0 3/0 4/0
Figure 4-5: Minimum Wire Sizes for DC Connections